Analysis of Different Types of Fire-Resistant Cable Trays

Currently, there are numerous differing perspectives and interpretations regarding Fire-resistant Cable Traysin the market. Our understanding is based on years of experience in cable tray applications.

Drawing on market experience and guided by an attitude of pursuing truth and striving for excellence, we have conducted evaluations of various types of Fire-resistant Cable Traysand identified instances of unauthorized replacements.

Analyze and explain the products under consideration, engage in discussions, and progress together.

According to the national standard "GB 29415-2013 Fire-resistant Cable Trunking", Fire-resistant Cable Traysare classified based on their fire resistance service duration.

There are four levels: F1 (≥90 minutes), F2 (≥60 minutes), F3 (≥45 minutes),

F4 (≥30 minutes). The critical aspect of Fire-resistant Cable Trayslies in their "operational duration" during a fire, which refers to:

Under fire exposure conditions and within the specified service life periods of different ratings, the cables inside the cable tray maintain their original functionality (power supply).

Control, measurement, signal transmission, etc.), to ensure immediate alarm activation, fuel source cutoff, fire suppression system initiation, and personnel evacuation.

Take appropriate measures to minimize fire losses. If a cable tray fails to meet the requirements for fire-resistant operation, it should be classified as a non-fire-resistant cable tray.

To meet the requirements for fire-resistant cable trays, the internal temperature of the tray must be maintained at approximately 200 degrees Celsius within the specified time frame.

If the voltage falls below this level, the insulation layer in the cable will lose its insulating function, rendering the cable ineffective and unable to meet its intended fire-resistant requirements.

The required operating time for level maintenance is fire-resistant.

In typical fire exposure environments where temperatures exceed 1000°C, how can the internal temperature be maintained below approximately 200°C? This is a critical consideration regarding the material selection for cable trays.

The materials and structure must primarily meet three critical requirements: 1. Excellent thermal insulation performance; 2. Superior sealing effectiveness; 3. Compliance with fire resistance specifications.

Maintain mechanical strength over time. Products manufactured under the fulfillment of the above three conditions generally meet the required fire resistance rating standards.

ask .

The main types of Fire-resistant Cable Trayscurrently available on the market include: coated Fire-resistant Cable Traysand inorganic fire-resistant cable trays.

Fire-resistant cable trays, mezzanine fire-resistant cable trays, and polymer composite fire-resistant cable trays. The following provides a detailed analysis of each of these products.

 

1. Coated fire-resistant cable tray

A fire-resistant material (i.e., fireproof coating) is applied externally to the metal cable tray. This material must rapidly expand and foam upon exposure to fire.

Sufficient volume increase creates gaps between the sealed cable trays, preventing heat conduction and achieving thermal insulation and sealing objectives. However, to achieve this...

To achieve this objective, the fire-resistant coating must possess sufficient thickness and strength (greater than 5 mm), which is challenging to accomplish in actual production processes.

The reasons are as follows: 1. Most coating materials consist of inorganic components, which are prone to delamination from the metal cable tray (due to thermal expansion) once they reach a certain thickness.

1. The coefficient varies; 2. Outdoor exposure to wind, rain, and sunlight also significantly increases the risk of powdering and detachment; 3. Costs have risen substantially.

As a result, there are very few Fire-resistant Cable Traysmade from fireproof coatings that meet the required standards in the market; most consist of a thin layer of fireproof coating.

This material absolutely fails to meet fire safety requirements.

 

2. Inorganic fire-resistant cable tray (manufacturers description)

Inorganic cable trays are manufactured from chloromagnesium cement; the inherent properties of this material determine that cable trays made from it are exclusively suitable for this purpose.

Non-flammable does not equate to fire-resistant (fireproof), and thus fails to meet the requirements for fire-resistant cable trays. Chloride-magnesium cement is non-flammable when exposed to fire.

Moreover, it should not foam to insulate thermal conduction or seal the gaps in the cable tray. Upon fire exposure, the internal temperature of the cable tray rises rapidly to 700–800 degrees Celsius.

The cables in such systems will quickly lose their original functionality and fail entirely to serve as fire-resistant cable trays. This type of product (material) is merely...

Tests that can be classified as flame retardancy grades for building materials cannot be conducted in accordance with the requirements for fire-resistant (fireproof) products; consequently, no fire resistance assessment is possible.

The levels are F1 to F4.

 

3. Mezzanine fire-resistant cable tray

The outer layer of the sandwich fire-resistant cable tray is made of non-combustible material, the inner layer is rigid material, and the middle layer is thermal insulation material. The joints are connected using...

The sheath and cover plate feature a laminated embedded structure.

Such Fire-resistant Cable Traysare rarely available in the actual market, as their complex manufacturing processes and high costs make them significantly more expensive than conventional fire-resistant cable trays.

The water ingress rate is 5–10 times higher, rendering the system impractical due to complex installation, significant space requirements (especially for outdoor installations), and high susceptibility to water infiltration in the mezzanine area.

The additional weight of the cable tray causes deformation, which increases the connection gaps between its components and consequently compromises its fire-resistant performance.

This has proven effective. Furthermore, the moisture in the cable trays interlayer readily corrodes the inner layer of the fire-resistant cable tray-which serves as the primary support structure.

As a result, sandwich Fire-resistant Cable Traysare rarely used in practice and seldom available on the market.

 

4. Polymer Composite Fire-Resistant Cable Tray

The cable tray structure features a metal steel lining, with an outer layer of 2–5 mm thick fire-resistant polymer material applied between them via a bonding layer and multiple extrusion processes.

The machine and composite mold perform one-step extrusion and drawing molding. Its characteristics include: 1. High degree of automation (automatic extrusion molding); 2. Environmental friendliness.

(Non-polluting and fully recyclable); 3. High strength (with a metal steel lining inside); 4. Easy installation, comparable to conventional models.

The installation process for cable trays is identical; 5. Low cost; 6. Excellent corrosion resistance; 7. Superior fire-resistant performance with high molecular fire retardancy.

Upon exposure to fire, the material immediately foams, providing thermal insulation and sealing all gaps between the cable trays, preventing flames from entering the trays.

Internally, this provides excellent fire resistance.

The above analysis reveals that: in terms of manufacturing processability, installation convenience, environmental friendliness, mechanical strength, corrosion resistance, and anti-corrosion performance...

In terms of fire performance, manufacturing cost, and other aspects, polymer composite Fire-resistant Cable Traysoutperform other types of fire-resistant cable trays.

 

 

Send Inquiry